WEKO3
アイテム
Design and operation of an air-conditioning system fueled by wood pellets
http://hdl.handle.net/10232/5082
http://hdl.handle.net/10232/5082349d9096-dd26-4ee3-86d2-a71342bbdcc7
| 名前 / ファイル | ライセンス | アクション |
|---|---|---|
|
|
|
| Item type | 学術雑誌論文 / Journal Article(1) | |||||
|---|---|---|---|---|---|---|
| 公開日 | 2010-10-05 | |||||
| タイトル | ||||||
| タイトル | Design and operation of an air-conditioning system fueled by wood pellets | |||||
| タイトル言語 | en | |||||
| 著者 |
Kai, Takami
× Kai, Takami× Uemura, Yoshimitsu× Teraoka, Yukio× Takahashi, Takeshige× Hatate, Yasuo× Yoshida, Masahiro |
|||||
| 言語 | ||||||
| 言語 | eng | |||||
| キーワード | ||||||
| 主題言語 | en | |||||
| 主題Scheme | Other | |||||
| 主題 | Wood pellets | |||||
| キーワード | ||||||
| 主題言語 | en | |||||
| 主題Scheme | Other | |||||
| 主題 | Space cooling | |||||
| キーワード | ||||||
| 主題言語 | en | |||||
| 主題Scheme | Other | |||||
| 主題 | Wood chips | |||||
| キーワード | ||||||
| 主題言語 | en | |||||
| 主題Scheme | Other | |||||
| 主題 | Absorption heat pump | |||||
| 資源タイプ | ||||||
| 資源タイプ識別子 | http://purl.org/coar/resource_type/c_6501 | |||||
| 資源タイプ | journal article | |||||
| アクセス権 | ||||||
| アクセス権 | open access | |||||
| アクセス権URI | http://purl.org/coar/access_right/c_abf2 | |||||
| 要約 | ||||||
| 内容記述タイプ | Other | |||||
| 内容記述 | A room-cooling system of 2 kW capacity fueled by wood pellets was designed, built and tested. The system was demonstrated during summer at the Yakushima Field Station of Kagoshima University, Japan. It contained a pellet feeder, a pellet burner, a heat exchanger, a lithium bromide.water absorption heat pump and a control unit. The volume of the test room was 36.9 m3 and ambient temperature 30 °C. The airflow temperature from the room unit was decreased to 16 °C by the system, and the room temperature could be successfully controlled to 24 °C steady state. Room heating in winter was also demonstrated. Since the air was heat exchanged, the overall energy efficiency of the cooling system was low at about 19%. However, the calculation based on the heat flow showed that the efficiency could be enhanced to about 75% by direct heating of the regenerator by the flue gas. |
|||||
| 内容記述言語 | en | |||||
| 収録雑誌名 |
en : Renewable Energy 巻 33, 号 4, p. 720-725, 発行日 2008-04-01 |
|||||
| 作成日 | ||||||
| 日付 | 2008-04-01 | |||||
| 日付タイプ | Issued | |||||
| ISSN | ||||||
| 収録物識別子タイプ | PISSN | |||||
| ISSN | 09601481 | |||||
| NII書誌ID(雑誌) | ||||||
| 収録物識別子タイプ | NCID | |||||
| NC ID | AA10802274 | |||||
| 出版タイプ | ||||||
| 出版タイプ | AM | |||||
| 出版タイプResource | http://purl.org/coar/version/c_ab4af688f83e57aa | |||||
| NDC | ||||||
| 主題Scheme | NDC | |||||
| 主題 | 570 | |||||
| 公開者・出版者 | ||||||
| 出版者 | Elsevier | |||||
| 出版者言語 | en | |||||